  compact power line 48v dc critical power solution the compact power line platform is designed to provide highly reliable dc power for 48v distributed power architectures. a single shelf configuration provides up to 11kw of 48v output power in 1u high and mounts in 19-inch or 23-inch wide frames. the CPL product platform is easily expandable for future growth. CPL is a reliable dc power solution for mission-critical enterprise and telecommunications network equipment. shelf options the cp product line provides several shelf options with common or split dc output configurations. there are two families of CPL shelves; one used with a pulsar edge controller, the other used without a controller or with a customers own controller using i 2 c communications. j85480s1 shelves have four slots for rectifiers or converters (pems) and use i 2 c for communications. j2007001 shelves have four slots with space for a full- feature pulsar edge controller. the pulsar edge controller has ethernet connectivity to facilitate remote network management to monitor and control rectifiers, batteries, and distribution. CPL is ideal for a broad range of applications requiring highly efficient 48v dc power. rectifier options cp2000 and cp2725 rectifiers are single phase, constant power rectifiers that provide 2000 watts and 2725 watts (respectively) of highly reliable dc power. the constant output power characteristics, extended temperature range, universal ac input, and compact size are key attributes that make this rectifier the right choice for your power needs. pulsar edge controller CPL features the pulsar edge controller delivering large system intelligence in a small system form factor. ethernet connectivity with snmp facilitates remote network management. features and benefits reliability ? proven field performance ? advanced alarming ? n+1 modularity intelligence ? industry leading controller features ? ethernet interface for remote access ? centralized network management investment protection ? minimal space requirements ? versatile configurations ? efficient operation on time delivery ? standard building blocks ? 8-16 week availability ? 24/7 support ? compact 48v dc distributed power system ? efciency approaching 97% ? maximum power in minimal space ? scalable to 80 kw ? powering enterprise and telecommunications networks
CPL power supplies applications key features specifications the CPL series of rectifiers are specifically designed to operate as an integral part of a complete distributed power system or can be easily integrated into an oem design. the high-density, front-to-back airflow rectifier is designed for minimal space utilization and is highly expandable for future growth. the power modules are available with many features including poe isolation, rs485 communications bus for use with ge battery plant controllers in forming an energy reserve system and redundant i 2 c communications bus for use with a customers controller. this flexible and sophisticated feature set makes this front-end power supply an excellent choice for power in a variety of application spaces. ? enterprise networks ? oem telecom equipment ? power over ethernet ? voip/soft switches ? san/nas/iscsi applications ? lan/wan/man applications ? indoor wireless ? routers and switches ? compact 1ru form factor ? pmbus compliant dual i 2 c and rs485 serial bus communications ? front panel led indicators ? internal variable-speed fan control ? constant power; 52 C 58 vdc ? programmable output voltage; 44 C 58 vdc ? universal ac input ? poe compliant versions available ? ce marked ? rohs 6 compliant ? hot pluggable ac-dc power supplies input 2000 2725 voltage range - low-line - high-line 120vac nominal (1200w) 208, 240, 277vac nominal input frequency 47 C 63 hz input current 11.9 arms @ 110vac 13.1 arms @ 240vac inrush transient 25apk typical power factor 0.98 from 50% to 100% load holdup time 20ms 1 , 30ms** emi/emc exceeds fcc and cispr22 (en55022) - class a 1 measurement starts at zero crossing of the ac voltage, and voltage devayed to 40v 2 for loads below 1200w 2 compact power line, cpb-CPL | gecriticalpower.com
ac-dc power supplies output 2000 2725 voltage default 54vdc voltage adjust range - hardware set via margin pin - i 2 c or rs485 set 44-58vdc 42-58vdc rated output current - low line - high line 25 1 38.4 2 25 1 52.4 2 rated output power - low line - high line 1200w 3 2000w 4 1200w 3 2725w 4 psophometric noise 9mvrms5 ripple (5hz to 20mhz) - rms - peak to peak 100mvrms max 250mvp-p max over voltage protection - delayed - immediate 60vdc 60vdc over temperature - warning - shutdown 5c 20c poe isolation optional optional 1 at 1200w, 54v @ 100-120vac 2 at full power @ 52v @ 200-240vac 3 at low line input from nominal 100-120vac 4 at high line input from nominal 200-277vac 5 complies with ansi ti.523-2001 section 4.9.2 emissions max limit of 20mv fat unweighted wideband noise limit dc-dc power supplies output 2000 2500 voltage range -40 to -72 vdc input current 60adc max 75adc max inrush current 60adc max 100adc max holdup time 6ms emi/emc exceeds fcc and cispr22 (en55022) - class a dc-dc power supplies output 2000 2500 voltage default 54vdc voltage adjust range 44 - 58 vdc rated output current 0.1 to 37a 0.1 to 46.3a rated output power 2000w 2500w ripple (5hz to 20mhz) - rms - peak to peak 250mvrms 500mvpk-pk over voltage protection - delayed - immediate 60vdc 65vdc over temperature - warning - shutdown 5c 20c poe isolation yes yes 3 compact power line, cpb-CPL | gecriticalpower.com
mechanical length (in./mm) 13.85 / 351.2 width (in./mm) 4 / 101.6 height (in./mm) 1.63 / 41.4 weight (lb / kg) 5 / 2.27 general cooling internal variable speed fan cooled efciency 90% @ 100 vac (vout>52v, pout>50% 93% @ 230 vac (vout>52v, pout) heat dissipation ac-dc 2725 -> 151w / 514 btu 2500 -> 138w / 471 btu 2000 -> 110w / 375 btu dc-dc 2500 -> 220w / 751 btu 2000 -> 176w / 601 btu environmental operating temperature -40oc 1 to +75oc (-40f to 167f) storage temperature -40c to +85c (-40f to 185f) power de-rating > +55c (derates @ 2% per c) relative humidity 95% max, non-condensing altitude 4,000m max (13,000 ft) audible noise 55dba, typical safety and standards compliance zone 4 per telcordia gr-63-core, all foors when installed in CPL shelf safety ce mark to low voltage directive 2006/95/ec ul 609501-1 recognized can/csa c22.2 no. 60950-1-03 certifed vde 0805-1 licensed to iec60950-1 rohs compliant to rohs eu directive 2002/95/ec emc fcc and cispr22 (en 55022) class a esd en/iec 61000-4-2 level 3 1 designed to start at an ambient as low as -40c but may not meet operational limits until above -5c. all ac-dc models and all dc-dc models 4 outline drawing symbol analog mode i 2 c mode rs485 mode on: input ok blinking : input out of limits on: output ok blinking : overload on : over-temperature warning on : over-temperature warning blinking : service on : over-temperature warning on : fault on: output ok blinking : overload dimensions front panel leds compact power line, cpb-CPL | gecriticalpower.com
applications key features ? enterprise networks - voice, data, poe ? telecommunications networks ? transmission equipment ? fiber in the loop ? routers/switches ? data networks ? pbx remote access and features ? integrated 10/100base-t ethernet network - tcp/ip - snmp v2c for management - smtp for email - telnet for command line interface - dhcp for plug-n-play - ftp for rapid backup and upgrades - http for standard web pages and browsers - compatible with galaxy manager and other management packages - shielded rj-45 interface referenced to chassis ground ? password protected security levels: user, super-user, administrator for all access ? ground-referenced rs232 system port ? ansi t1.317 command-line interface ? modem access support - remote via external modem - callback security ? easyview2, windows-based gui software for local terminal or modem access standard system features ? monitor and control of more than 40 connected devices - maximum of 32 rectifers - maximum of 6 distribution control cards - robust rs485 system bus ? standard and user defned system alarms - alarm test - assignable alarm severity: critical, major, minor, warning, and record-only ? rectifer management features - automatic rectifer restart - active rectifer management (energy efciency) - remote rectifer (on/of) - reserve operation - automatic rectifer sequence control - n + x redundancy check ? multiple low voltage load and low voltage battery disconnect thresholds (4) ? confguration, statistics, and history - all stored in non-volatile memory - remote/local backup and restore of confguration data ? industry standard defaults - customer specifc confgurations available ? remote/ local software upgrade ? basic, busy hour, and trend statistics ? detailed event history ? user defned events and derived channels standard battery management features ? float/boost mode control - manual boost - manual timed boost locally, t1.317, and remotely initiated - auto boost terminated by time or current ? battery discharge testing - manual (local/remote) - periodic - plant battery test (pbt) input driven - confgurable threshold or 20% algorithm - graphical discharge data - rectifers on-line during test ? slope thermal compensation - high temperature - low temperature - step temperature - stc enable/disable, low temperature enable/disable - confgurable mv/c slopes ? state of charge indication ? high temperature disconnect setting ? reserve-time prediction ? recharge current limit ? emergency power-of input 5 pulsar edge controller (for applications in j2007001 shelves) the CPL pulsar edge controller delivers large system intelligence in a small system form factor. this family of controllers functions as a network interface controller (nic) and as a full-featured battery plant controller to the compact power line (CPL) platform. its thin modular plug-in form factor minimizes shelf space consumption allowing maximum power module and distribution capabilities yet provides features found in controllers used in much larger power systems. the pulsar edge cp841a controller is utilized in bulk power applications in data centers and enterprise applications. ethernet connectivity with snmp facilitates remote network management access through its front-accessible rs232 or usb port and is aided by the easyview2 graphical user interface. as a battery plant controller, it provides a complete set of features to monitor and control rectifiers, batteries, and distribution. a flexible set of configurable inputs allow the cp841a to monitor a wide variety of system equipment and incorporate appropriate state information enabling a centralized point of management. the controller utilizes standard network management protocols allowing for advanced network supervision. ge galaxy manager* software is the centralized visibility and control component of a comprehensive power management system designed to meet engineering, operations, and maintenance needs. the galaxy manager client-server architecture enables remote access to system controllers across the power network. * see next page for galaxy manager description compact power line, cpb-CPL | gecriticalpower.com
6 general operating voltage 24 vdc, 48 vdc (range: 18 to 60 vdc) input power less than 7w operating temperature range -40c to +75c (-40f to 167f) storage temperature range -40c to +85c (-40f to 185f) operating relative humidity 0 - 95% (non-condensing) physical specifcations 1.75 in. h, 0.75 in. w, 8.00 in. d; 0.5lb 45mm h, 20mm w, 204mm d; 227g display 8-line by 40-character backlit lcd agency certifcations radiated emissions fcc, class b; en 55022, class b safety ul unlisted component as part of CPL or sps power system rohs compliant to rohs eu directive 2002/95/ec emc fcc/en55022 class b, cispr22 level b esd en 61000-4-2 level 4 integrated monitoring inputs/outputs ? system plant voltage (accuracy 0.5%, resolution 0.01v) ? one system shunt (accuracy 1% full scale, resolution 1a) - battery or load - mounted in the return side of dc bus ? up to 15 binary inputs - six inputs close/open to battery - 9 input close/open to return (number is dependent upon number of output alarms) - user assignable ? up to 5 user assignable form-c output alarms (50vdc @ .3a) ? 1-wire* bus devices - up to 16 temperature probes (qs873) - up to 6 mid-string monitors (es771) galaxy manager compatible ? centralized web server and database with multiple user access to live or managed data with drill down to problem details ? monitor and control of more than 40 connected devices ? management information from polling or alarms received from alarm traps from multiple sites are available on one screen via the inter/intranet ? trend user selected data over time ? automatic or manual report generation ? standard engineering tools like reserve time calculators and cable voltage drop analyzer compact power line, cpb-CPL | gecriticalpower.com
48v dc critical power solution features C model j85480s1 features C model j2007001 the compact power line platform is designed to provide highly reliable dc power for 48v distributed power architectures. when embedded into an oem design, ge can support the integration into the oem design, otherwise an external shelf can be used to provide power. a single shelf configuration provides up to 11kw of 48v output power in 1u high and mounts in 19-inch or 23-inch wide frames. the CPL product platform is easily expandable for future growth by stacking multiple shelves. CPL is a reliable dc power solution for mission-critical enterprise and telecommunications network equipment. the CPL product line provides several shelf options. j85480s1 shelves have four slots for either rectifiers or converters (pems). these shelves are primarily used without a controller or with a customers controller using i 2 c communications. j2007001 shelves have four slots with space for a full-feature pulsar edge network interface controller (nic). the pulsar edge controller has ethernet connectivity with snmp to facilitate remote network management to monitor and control rectifiers, batteries, and distribution. these shelves are used with either shelf mounted distribution or external distribution panels for small battery plant applications. ? fits into a standard 19 rack ? two dc outputs may be common or split. each output bus is rated for 100a with two-hole lug landings for 2 awg wire. ? choose between iec-320 c13 or c19 or other ac input connections. ? analog or dual/redundant i 2 c communications. ? adjustable mounting ears for near flush front or multiple set back positions. ? fits into a standard 19 rack ? single dc output rated for 200a with two-hole lug landings for up to 2/0 awg cable. ? choose between iec-320 or molex mini-fit sr for ac input. single, dual or quad input feeds ? rs485 communications. ? adjustable mounting ears with multiple set back positions. ? up to 3 shelves may be interconnected with bus straps for dc outputs for a 600a system ? plug-n-play cp841a controller with front access craft port, rear access lan and alarm connections ? select shelves include distribution modules j2007 rectifier shelf j2007 converter shelf j85480 rectifier shelf j85480 converter shelf 7 ordering information C compact power line compact power line, cpb-CPL | gecriticalpower.com
8 shelf line drawing C j85480s1shelves list max power dc input plug dc output max power supply features order code bus termination setpoint other 14 10kw qty 2 (1 per 2 rectifers) split dh lugs cp2500dc (+) 48vdc poe, analog, i 2 c cc109124764 list max power ac input plug dc output max rectifer size features order codes bus termination setpoint other 20 11kw iec-320, c19 common dh lugs cp2725 (+) 54vdc analog, i 2 c cc109147344 21 split -54vdc cc109147328 23 8kw iec-320, c13 common cp2000 (+) 54vdc poe, analog, i 2 c cc109150447 j85480s1 shelf options ? list 25 shelves are preprogrammed to be always on. either polarity can be grounded. ? split shelves l21 and vout (-) is split, however vout (+) is paralleled among the 4 rectifiers. vout (+) should be grounded. ? all lists, up to 2 shelves can be paralleled for a single i 2 c line. up to eight shelves may be paralleled for current shared power delivery. ? all lists, shelf configured set point ensures inter-operability among all rectifiers from cp2000 to cp2725. rectifiers will proportionately current share relative to their output power capacity. ? all shelves are rohs 6 compliant. order should reflect j85480s1lxxz where xx is the list number and z indicates compliance to rohs 6. notes: compact power line, cpb-CPL | gecriticalpower.com
9 description schematic common output bus for terminal lug connection ? each lug connection rated for 100a with 2 gauge wire (200a for shelf) split output bus for terminal lug connection ? vdc( - ) has split buses vdc( + ) is common to both sections. ? each bus may be independently controlled ? multiple shelves may not be paralleled together. ? each lug connection rated for 100a with 2 gauge wire (200a for shelf) j1 connector C pin out pin signal pin signal 1 power_cap_1 16 sda_1 2 power_cap_2 17 fault 3 power_cap_3 18 alert#_0 4 power_cap_4 19 enable side b 5 mod_pres_1 20 logic_grd 6 mod_pres_2 21 enable side a 7 mod_pres_3 22 logic_grd 8 mod_pres_4 23 alert#_1 9 pfw_1 24 5va 10 pfw_2 25 otw 11 pfw_3 26 reset 12 pfw_4 27 iso. barrier n/c 13 scl_0 28 iso. barrier n/c 14 scl_1 29 shelf_addr_b 15 sda_0 30 shelf_addr_a j2 connector C pin out pin signal pin signal 1 scl_0 8 alert#_1 2 scl_1 9 isolation n/c 3 sda_0 10 isolation n/c 4 sda_1 11 ishare - b 5 alert#_0 12 ishare - a 6 5va 13 8v_int - b 7 logic_grd 14 8v_int - a dc output types C j85480s1 shelves communication signals C j85480s1 shelves compact power line, cpb-CPL | gecriticalpower.com
10 shelf line drawing C j2007001 shelves list max rectifer size ac input dc output rear view of shelf 3 2725 watts single ac feed (terminal blocks for 6ga wire and ? conduit ftting) dc output bus is rated for 200a for two 2ga or one 2/0 gauge two- hole lugs (?-20 studs on 5/8 centers). dc output bus ac signal 4 2725 watts individual feed (molex mini-fit sr) 6 2725 watts individual feed (iec-320 c19 cords) j2007001 shelf options 1. cp841a pulsar edge controller ships separately. 2. up to 3 shelves may be interconnected. notes: list max power dc input plug dc output max power supply features order code bus termination setpoint other 14 10kw 2 x ?-20 x 5/8 in dh lug common 2 x ?-20 x 5/8 in dh lug cp2500dc variable, set by edge controller rs485 cc109157657 j2007001l14 dc pem shelf options compact power line, cpb-CPL | gecriticalpower.com
11 j2007001 shelves system controller overview communication signals for j2007001 shelves battery monitoring j1 connector C pin out pin signals for sps841a_3c3r signals for sps841a_0i5r 1 alm1 input alarm relay 3 rtn 2 alm2 input alarm relay 2 rtn 3 alarm relay 1 rtn alarm relay 1 rtn 4 power minor rtn power minor rtn 5 power major rtn power major rtn 6 alm1, 2, 6c rtns alarm relay 3 7 alm6 input alarm relay 2 8 alarm relay 1 alarm relay 1 9 power minor power minor 10 power major power major edge controller cp841a_3c3r j1 has 3 alarm inputs with a common return and 3 output relays; power major, power minor, 1 selectable j2 connector pin signal 1 alm6 input 2 - 3 alm3 input 4 alm4 input 5 alm5 input 6 -48v 7 -48v 8 -48v j7 connector pin signal 1 faj 2 coil rtn 3 lvd_nc 4 lvd_no 5 shunt- 6 os 7 coil1 8 coil2 9 lvd status rtn 10 shunt+ ? j1 provides alarm outputs and inputs based on the controller installed (see table below). inputs are dry, no voltage, contact closures or opens to a common return on pin 6. outputs are relay contacts. both input and output alarms are customer defined on the controllers web pages. ? j2 provides alarm inputs (see table below). alarm inputs are contact closures or opens to the non-grounded side of the dc bus [-48v]. pins 6, 7, 8 provide -48v for these alarm inputs. ? j3 battery thermal probe (qs873a) or battery mid-string voltage monitor (es771) with battery thermal probe. ? j4 shelf to shelf communication connection ? j5 lan/ethernet. ? j7 provides distribution control for shelves with external distribution. see table below. temperature/voltage probes are needed for battery monitoring. they are connected to each battery or battery string to provide slope thermal compensation, temperature alarms and voltage imbalance alarms. refer to ordering guide for diagram and part numbers. ? compact power line, cpb-CPL | gecriticalpower.com
12 ? communication cables 10 communication cable (j1) cc848854034 shelf to shelf communication cable (j2) cc848848952 rectifer cp2000ac54tez cc109158440 cp2000ac54tep cc109167565 cp2725ac54tep cc109167532 cp2725ac54tez cc109149423 rectifer slot filler central oce white cc848822263 converter (pem) options cp2000dc54pez cc109162104 cp2500dc54pez 1 cc109170528 rectifer slot filler central oce hite cc848822263 rectifer shelf options list 20 cc109147344 list 21 cc109147328 list 23 cc109150447 for more options see page 7 converter shelf options list 14 cc109124764 mounting brackets 1u bracket for 23 frame mount cc848844803 2u bracket for 23 frame mount 848683009 wall mount bracket cc848864504 mounting brackets 1u bracket for 23 frame mount cc848844803 wall mount bracket cc848864504 dc input cables dc input cable, 10 ga, 4 cc848794908 dc output cables dc output cable, 2 ga 10 848748987 dc bus for 1/4 faston connections (2 required) cc848886192 ac input, dc output cables c13 plug with 5-15p plug, 10 cc848776105 c13 plug with l6-20p plug, 10 cc848820317 c13 plug, unterminated, 10 847861192 c19 plug, with 5-15p plug, 8 cc848850792 c19 plug, with l6-20p plug, 8 cc848850842 c19 plug, unterminated, 8 cc848847368 dc output cable, 2 ga, 10 848748987 ac dc j85480s1 shelf ordering guide j85480s1 converter shelf ordering guide compact power line, cpb-CPL | gecriticalpower.com ?
13 converter (pem) options cp2000dc54pez cc109162104 cp2500dc54pez 1 cc109170528 rectifer slot filler central ofce white cc848822263 converter shelf options list 14 cc109157657 controller cp841a_3c3r cc109145331 slot filler cc848847871 mounting brackets 1u bracket for 23 frame mount cc848844803 wall mount bracket cc848864504 dc output cables dc output cable, 2 ga 10 848748987 dc bus for 1/4 faston connections (2 required) cc848886192 j2007001 converter shelf ordering guide alarm and communication cables 15 alarm or distribution cable (j1 or j7) cc848865980 50 alarm or distribution cable (j1 or j7) cc848817651 150 alarm or distribution cable (j1 or j7) cc848817668 15 alarm input cable (j2) cc848853614 shelf to shelf communication cable (j3, j4) cc848847780 rectifer shelf options list 3 cc109147542 list 4 cc109140043 list 6 (shown) cc109140027 rectifer cp2000ac54tez cc109158440 cp2000ac54tep cc109167565 cp2725ac54tep cc109167532 cp2725ac54tez cc109149423 rectifer slot filler central ofce white cc848822263 mounting brackets 1u bracket for 23 frame mount cc848844803 2u bracket for 23 frame mount 848683009 wall mount bracket cc848864504 ac input, dc output cables c19 plug, with 5-15p plug, 8 cc848850792 c19 plug, with l6-20p plug, 8 cc848850842 c19 plug, unterminated, 8 cc848847368 molex mini-fit sr, unterminated, 8awg, 10 (2 cables provided) 848710711 dc output cable, 2ga, 10 848748987 dc bus bar strap (2 required) cc848844324 ac dc j2007001 shelf ordering guide controller cp841a-3c3r cc109145331 ? ? compact power line, cpb-CPL | gecriticalpower.com
14 power module output power/input voltage output voltage protection physical cp2000ac54tez/tep 2000w / 200-277vac 1200w / 100-120vac hardware set 44 - 58vdc software set 42 - 58vdc 15a breaker, 14 gauge wire length: 13.85/351.8mm width: 4.00/101.6mm height: 1.66/42.2mm weight: 4.6lb/2.1kg cp2500dc54pez 2500w / 40-72vdc 70a breaker, 8 gauge wire cp2725ac54tez/tep 2725w / 200-277vac 1200w / 100-120vac 20a breaker, 12 gauge wire cp2000dc54-pe 2000w / 40-72vdc 60a breaker, 8 gauge wire mechanical j85480s-1 j2007001 height 1.71inches/43.4mm 1.71 inches/43.4mm width (with mounting ears) 19 inches/483mm 19 inches/483mm depth 16.25 inches/413mm 17.06 inches/433mm weight (without rectifers) 9.25lbs/4.2kg 8.75lbs/4.0kg environmental j85480s-1 j2007001 operating temperature range list 14: -40c to 75c (-40 to 167 f) lists 20, 21: -40c to 25c (-40 to 77 f) [commercial 60c c19 ac cord] -40c to 55c (-40 to 131 f) [high temp c19 ac cord] lists 23: -40c to 25c (-40 to 77 f) [commercial 60c c13 ac cord] -40c to 55c (-40 to 131 f) [high temp c13 ac cord] lists 6: -40c to 25c (-40 to 77 f) [commercial 60c c19 ac cord] -40c to 55c (-40 to 131 f) [high temp c19 ac cord] lists 3, 4: -40c to 55c (-40 to 131 f) operating relative humidity 0 - 95% (non-condensing) storage temperature range -40c to 85c (-40 to 185 f) emc fcc, en 55022, cispr22, level a, conducted and radiated immunity en55024 (cispr24) class a, conducted and radiated safety/standards compliance j85480s-1 j2007001 safety standards can/csa c22.2 no. 60950-1-03, ul 60950-1, 1st edition vde iec 60950-1, 1st edition certifcation marks lists 14, 20, 21, 23 vde lists 14 ul recognized (canada and u.s.) lists 20, 21, 23 ul listed (canada and u.s.) lists 4, 6 vde lists 4 ul recognized (canada and u.s.) lists 6 ul listed (canada and u.s.) specifcations rectifiers shelves notes : pe suffix denotes poe compliance. z suffix denotes rohs 6 compliance. te suffix denotes total efficiency* architecture. note: all ge cp ac cords are high temperature cords. battery management accessories a: qs873a thermal probe cc109142980 b: 10 probe to controller wireset cc848817024 c: 1 probe to probe wireset cc848822560 c: 5 probe to probe wireset 848719803 c: 10 probe to probe wireset cc848822321 es771a voltage monitor card 108958422 d: 2 ? es771a to probe wireset cc848791517 d: 6 es771a to probe wireset cc848797290 d: 10 es771a to probe wireset 848719829 g: 4 es771a to es771a or controller wireset cc848791500 g: 10 es771a to es771a or controller wireset 848652947 compact power line, cpb-CPL | gecriticalpower.com
15 notes compact power line, cpb-CPL | gecriticalpower.com
compact power line, cpb-CPL, rev. 02/14 *trademark of general electric company. copyright 2014 general electric company. all rights reserved. ge reserves the right to make changes to specifcations of products described at any time without notice and without obligation to notify any person of such changes. management visibility galaxy manager* software is the centralized visibility and control component of a comprehensive power management system designed to meet engineering, operations and maintenance needs. the galaxy manager client-server architecture enables remote access to system controllers across the power network. ? dashboard display with one-click access to management information database ? trend analysis ? scheduled or on demand reports ? fault, configuration, asset, and performance management training ge offers on-site and classroom training options based on certification curriculum. technical training can be tailored to individual customer needs. training enables customers and partners to more effectively manage and support the power infrastructure. we have built our training program on practical learning objectives that are relevant to specific technologies or infrastructure design objectives. service & support ge field service and support personnel are trusted advisors to our customers C always available to answer questions and help with any project, large or small. our certified professional services team consists of experts in every aspect of power conversion with the resources and experience to handle large turnkey projects along with custom approaches to complex challenges. proven systems engineering and installation best practices are designed to safely deliver results that exceed our customers expectations. warranty ge is committed to providing quality products and solutions. we have developed a c omprehensive warranty that protects you and provides a simple way to get your products repaired or replaced as soon as possible. for full warranty terms and conditions please go to www.gecriticalpower.com . 601 shiloh road, plano, tx 75074 +1 877 546 3243 (toll-free in north america) +1 972 244 9288 (direct number) info.criticalpower@ge.com gecriticalpower.com 24/7 technical support pe.techsupport@ge.com